The Type 590X I/P (current to pressure) transducer converts a variable electrical signal to a linearly proportional pneumatic output. The small size, light weight and immunity to shock and vibration make it ideal for use in process control applications.

Conversion technology utilizing open loop control and a low mass magnet produces accurate pressure control at an economical cost. The Type 590X can mount in any position and is impervious to RFI/EMI interference.

Multiple choices for wiring and porting simplify installation and decrease the time required to do so. In addition to standard wall, panel or pipe mounting, optional DIN rail and manifold mounting kits are available.

Request a Quote
Availability: In stock
SKU
CA01500W

The Type 590X I/P (current to pressure) transducer converts a variable electrical signal to a linearly proportional pneumatic output. The small size, light weight and immunity to shock and vibration make it ideal for use in process control applications.

Conversion technology utilizing open loop control and a low mass magnet produces accurate pressure control at an economical cost. The Type 590X can mount in any position and is impervious to RFI/EMI interference.

Multiple choices for wiring and porting simplify installation and decrease the time required to do so. In addition to standard wall, panel or pipe mounting, optional DIN rail and manifold mounting kits are available.

SPECIFICATIONS

Input

4-20 mA

Output Range

3-15 psig (0.20-1.0 bar), 3-27 psig (0.20-1.8 bar), 6-30 psig (0.40-2.0 bar)

Air Consumption

6 scfh (170 Nl/hr)

Max. Supply Pressure

42 psig (2.8 bar)

Flow Capacity

2.4 scfm (67.92 Nl/min)

Ambient Temperature Limits

-40° to +158°F (-40° to +70°C), -67° to +158°F (-55° to +70°C)

Relative Humidity

75% average – 95% short time non-condensing

Impedance

260 Ohms @ 70°F (21°C)

Loop Load

5.2 volts @ 70°F (26°C)

Linearity (Independent)

<+ 0.5% of span

Hysteresis

<+ 0.3% of span

Deadband

<+ 0.1% of span

Repeatability

<+ 0.3% of span; <+ 0.15% of span typical

Mounting Orientation

<+ 0.5% / 90 degree change (metric)

Air Supply Sensitivity

<+ 0.3% per 1.5 psig change

Vibration Effect

<+ 1% up to 10g and 20-80 Hz.

Temperature Effect

<+ 0.75% / 10°F change (metric)

Housing

Nema 1 (IP 20)

Port Size

1/8" NPT

Media

Clean, dry, oil-free, instrument air, filtered to 40 micron

Electrical Connection

Terminal block

Mounting

Pipe, DIN rail

Materials (Body)

Aluminum, Plastic

Materials (Other)

Buna-N, Stainless Steel, Brass, Zinc-plated Steel, Polypropylene